ErP 2016/18

ErP 2016/18
Euroclima informs...
about ErP directive
When
What
The European regulation EU No. 1253/2014
is implementing the Ecodesign requirements
from the European directive 2009/125/EG
for non-residential ventilation units. Non
residential units are divided n BVU and UVU.
Step 2
Step 1
01.01.2018
Abb: UVU
Unidirectional Ventilation Unit
01.01.2016
Abb: BVU
Bidirectional Ventilation Unit
Where
European Union
Member States
Exemptions
• Unit for delivery out of European Union
• Unit exclusively operating for emergency use
• Unit without fan (valid if supply-/ exhaust fan
or both)
• Unit exclusively working with recirculating air
• Unit for ships/cruise vessels (non building
application)
• Unit exclusively working in/with a potentially
explosive atmosphere as defined in Directive
94/9/EC (valid if supply-/exhaust air or both)
• Unit exclusively working in/with toxic or highly
corrosive or flammable or abrasive air
• Unit exclusively working with air temperature
>100°C
• Unit includes a heat exchanger and a heat
pump for heat recovery acc. EU No. 1253/2014
article 1.1 (g)
• …others (less important)
y
Components
HRS system with
thermal bypass facility
BVU
minimum thermal
efficiency of HRS
BVU
HRS efficiency
bonus E [W/(m³/s)]
BVU
all other HRS
run-around coil HRS
01.01.2016
01.01.2018
mandatory
mandatory
67 %
73 %
63 %
68 %
all other HRS
(ƞt-0,67)*3000
(ƞt-0,73)*3000
run-around coil HRS
(ƞt-0,63)*3000
(ƞt-0,68)*3000
HRS system
Reasonable thermal bypass method
Crossflow plate heat exchanger
mechanical bypass needed
Double plate heat exchanger
mechanical bypass needed
Heat wheel
control wheel rpm or stop wheel
Counterflow plate heat exchanger
mechanical bypass needed
Accumulator
stop switching between acumulator masses
Heatpipe
variable inclination
High performance run around coil
control medium flow or stop pump
Run around coil
control medium flow or stop pump
Non residential ventilation units requirements acc. EU 1253/2014
01.01.2016
01.01.2018
Final filter pressure alarm
or visual signaling
all
-
mandatory
Variable fan speed drive
or multispeed drive
all
mandatory
mandatory
for reference configuration
Filter correction value
F [W/(m³/s)]
Minimum fan efficiency ƞvu
(P...electrical absorbed
power including controls)
Maximum internal
specific fan power
of ventilation
components
SFPint_limit [W/(m³/s)]
all
UVU
0
160
150
if fine (F7) filter is missing
200
190
if both filters are missing
360
340
Pabs<=30 kW
6,2[%]*In(P)+35
6,2[%]*In(P)+42
Pabs>30 kW
56,1 %
63,1 %
UVU
BVU
HRS system with
thermal bypass facility
BVU
minimum thermal
efficiency of HRS
BVU
HRS efficiency bonus
E [W/(m³/s)]
0
if medium (M5) filter is missing
BVU
run-around
coil HRS
all other
HRS
q<2m³/s
250
230
1700+E-300*qnom/2-F
1600+E-300*qnom/2-F
q>=2m³/s
1400+E-F
1300+E-F
q<2m³/s
1200+E-300*qnom/2-F
1100+E-300*qnom/2-F
q>=2m³/s
900+E-F
800+E-F
mandatory
mandatory
67 %
73 %
all other HRS
63 %
68 %
all other HRS
run around coil HRS
(ƞt-0,67)*3000
(ƞt-0,73)*3000
run-around coil HRS
(ƞt-0,63)*3000
(ƞt-0,68)*3000
Euroclima group factories
Euroclima AG | SpA
St. Lorenzner Str. | Via S. Lorenzo 36
39031 Bruneck | Brunico (BZ)
ITALY
Tel. +39 0474 570 900
Fax +39 0474 555 300
office@euroclima.it
www.euroclima.com
Euroclima Apparatebau Ges.m.b.H.
Arnbach 88
9920 Sillian
AUSTRIA
Tel. +43 (0) 48 42 66 61 -0
Fax +43 (0) 48 42 66 61 -24
info@euroclima.at
www.euroclima.com
Bini Clima S.r.l.
Via Giovanni a Prato, 4
38068 Rovereto
ITALY
Tel. +39 0464 437 232
Fax +39 0464 437 298
info@biniclima.eu
www.biniclima.eu
Euroclima India Pvt Ltd.
Oberoi Garden Estate, B-Wing, 2nd floor
2059, Chandivali, Andheri (East)
400072 Mumbai
INDIA
Tel. +91 22 4015 8934 / 4022 6263
info@euroclima.in
www.euroclima.com
Euroclima product catalogues
ZHK 2000
CUSTOMIZED AIR HANDLING UNITS
HIGHEST EFFICIENCY AIR HANDLING UNIT
HIGH EFFICIENCY AIR HANDLING UNITS
ETA PAC
CLEANLINE
EnvironmEnt friEndly and clEan concEpt solutions
for comfort, hospital and industrial applications
packaged energy recovery solutions for green buildings
integrated accumulator, controls and dX cooling system
packaged energy recovery solutions for green buildings
integrated adiabatic cooling, controls and dx cooling system
COMpaCt & hygieniC sOlutiOns fOr Operating theaters
integrated COntrOls and dx COOling systeM
ETA POOL
df>
> 90 %
Efficiency
T1/TB1
optional
ASEPSIS
ETA ACCU
ZHK FI
KITCHEN
DEHUMIDIFICATION AIR HANDLING UNITS
HYGIENIC AIR HANDLING UNITS
HYGIENIC AIR HANDLING UNIT
EXHAUST FILTRATION UNIT
solutions for swimming pools
fully washable & free cold bridge design
for food and low temperature applications
FULLY WASHABLE UNITS FOR FOOD AND BEVERAGE INDUSTRY
SAINLESS STEEL; FULLY WELDED AND ROUNDED CORNERS TUNNEL
solutions for KitCHEn EXHAust Air
ETA MATIC
DX CIRCUIT
ZHK MARINE
solutions for MArinE AnD offsHorE
CONTROL SYSTEM FOR AIR HANDLING UNITS
intelligent unit mounted controls
for comfort, hospitals and industrial applications
REFRIGERANT COOLING SYSTEM
FOR AIR HANDLING UNITS
Euroclima October 2015
Due to it’s commitment of continuous product
development and improvement, Euroclima reserves
the right to change specifications without notice.
© Copyright by euroclima.com / fotolia.com
Filter Safe®
CUSTOMIZED AIR HANDLING UNITS
leak-proof hepa filter frames
for hospitals and clean room applications
MEDICAL AIR HANDLING UNIT
AIRWALL
SHUT-OFF, MIXING AND BALANCING DAMPERS